The last longer going power outage happened in August 2023. Today, whole city Langen was without power from 14:04 till 14:07 CEST. This affected everything which has no backup supply. Tornado Datacenter has diverse UPS for this case, one on A one on B Feed connected to central datacenter power distribution, which can change power sources from public grid (default mode) to generator (backup mode).
Also a emergency generator is available to take over the loads in case of a longer going outage, providing sufficient spare fuel. Load transfer can happen after 20 seconds public grid outage, until that, the UPSes are taking over IT load. Generator fuel delivery is SLA guaranteed.
Air Conditioning devices arent UPS protected, which is best practice in a modern datacenter environment. Not to mention the power draw of these, slowness of air temperature changes allow for restarts of cold air / water generation units, without breaching SLA or causing dangerous situations. A restart is caused whenever power is lost and/or transferred. During todays power outage, customers may have noticed a short spike in temperature, which was still below 30°C.
Beside of the restart of air conditioning equipment, the infrastructure remained operational.